Unit V
Unit V
UNIT-V
1
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – V: BASICS OF POWER SYSTEMS
2
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – V: BASICS OF POWER SYSTEMS
Generating station:
In the generating station, electric power is produced by 3-phase alternators.
The usual generation voltage is 11 kV.
The generation voltage is stepped-up to 220 KV at the generating station with help of
3-phase transformers.
Advantages of high voltage transmission:
The saving of conductor material
High transmission efficiency
Disadvantages of high voltage transmission:
It introduces insulation problems
The cost of switchgear and transformer equipment is increased
The primary transmission is carried at 66 KV, 132 KV, 220 KV, 400 KV or 765 KV.
The highest transmission voltage adopted for power transmission in India is 765 KV.
Primary transmission:
The electric power at 220KV is transmitted by 3-phase, 3-wire overhead system. This
forms the primary transmission.
Secondary transmission:
The primary transmission line terminates at the receiving station (RS).
At the receiving station, the voltage is reduced to 33 KV by step-down transformers.
From this station, electric power is transmitted at 33 KV by 3-phase, 3-wire overhead
system to various sub-stations (SS). This forms the secondary transmission.
Primary distribution:
The secondary transmission line terminates at the sub-station (SS), where voltage is
reduced from 33 kV to 6.6 KV by step-down transformer.
The 6.6KV lines run along the important road sides of the city. This forms the primary
distribution.
Big consumers (>50 kW) are supplied power at 6.6KV with their own sub-stations.
Secondary distribution:
The electric power from primary distribution line (6.6KV) is delivered to distribution
sub-stations (DS).
These distribution sub-stations are located near the consumer localities.
Here, step down the voltage to 400 V, 3-phase, 4-wire for secondary distribution.
The voltage between any two phases is 400 V and between any phase and neutral is
230 V.
3
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – V: BASICS OF POWER SYSTEMS
The single-phase residential lighting load is connected between any one phase and
neutral.
3-phase, 400V motor load is connected across 3-phase lines directly.
The secondary distribution system consists of feeders, distributors and service
mains.
2. DISTRIBUTION SYSTEM:
The part of power system which distributes electric power for local use is known as
distribution system.
In general, the distribution system is the electrical system between the sub-station fed
by the transmission system and the consumer’s meters.
It generally consists of feeders, distributors and the service mains.
Fig. 1.2 shows the elements of low voltage distribution system.
Feeders:
A feeder is a conductor which connects the sub-station (or localized generating station)
to the area where power is to be distributed.
Generally, no tapings are taken from the feeder so that current in it remains the same
throughout.
The main consideration in the design of a feeder is the current carrying capacity.
Distributor:
A distributor is a conductor from which tapping’s are taken for supply to the
consumers. In Fig. 1.2, AB, BC, CD and DA are the distributors.
The current through a distributor is not constant because tappings are taken at
various places along its length.
4
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – V: BASICS OF POWER SYSTEMS
While designing a distributor, voltage drop along its length is the main consideration
since the statutory limit of voltage variations is ± 6% of rated value at the consumer’s
terminals.
Service mains:
The service mains are generally a small cable which connects the distributor to the
consumers’ terminals.
5
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – V: BASICS OF POWER SYSTEMS
Advantages:
Simplest.
The initial cost is low.
Useful when the generation is at low voltage.
Preferred when the station is located at centre of the load.
Disadvantages:
The end of distributor near to the substation gets heavy loaded.
When load on the distributor changes, the consumer faces serious voltage
fluctuations.
As consumers are dependent on single feeder and distributor, a fault on any of these
two causes interruption in supply.
Drawbacks:
A distributor nearest to the substation is heavily loaded.
Due to load variation, voltage fluctuations are more at the far ends.
If any fault occurs, there is no continuity of supply.
The feeder in the ring fashion is divided into number of sections as AB, BC, CD, DE and
EA.
The various distributors are connected at A, B, C, D and E.
Each distributor is supplied by the two feeders.
7
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – V: BASICS OF POWER SYSTEMS
Advantages:
Due to load variations, the voltage fluctuation is less at the far end.
Better reliability.
It gives continuity of supply, when fault occurs at any one distributor.
Interconnected system:
When the feeder ring is energized by two or more than two generating stations or
substations is called as interconnected system.
Advantages of Interconnected System:
Better reliability.
During peak load, reserve power capacity reduces and efficiency increases.
It gives continuity of supply.
4. AC DISTRIBUTION SYSTEM:
8
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – V: BASICS OF POWER SYSTEMS
It is that part of AC distribution system which operates at voltages higher than general
utilization.
It handles large blocks of electrical energy than the average low voltage consumer uses.
The voltage used for primary distribution depends upon the amount of power to be
conveyed and the distance of the substation required to be fed.
The most commonly used primary distribution voltages are 11 kV, 6·6 kV and 3·3 kV.
Due to economic considerations, primary distribution is carried out by 3- phase, 3-wire
system.
Electric power from the generating station is transmitted at high voltage to the
substation located in or near the city.
9
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – V: BASICS OF POWER SYSTEMS
10
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – V: BASICS OF POWER SYSTEMS
6. EARTHING:
The process of connecting the metallic frame (i.e., non- current carrying part) of
electrical equipment or some electrical part of the system (e.g., neutral point in a star-
connected system) to the earth is called grounding or Earthing.
The potential of the earth is to be considered zero for all practical purposes.
Earthing is to connect any electrical equipment to earth with a very low resistance wire,
making it to attain earth’s potential.
This ensures safe discharge of electrical energy due to failure of the insulation line
coming in contact with the casing, etc.
Earthing brings the potential of the body of the equipment to zero i.e., to the earth’s
potential, thus protecting the operating personnel against electrical shock.
11
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – V: BASICS OF POWER SYSTEMS
Necessity of Earthing:
The requirement for provision of earthing can be listed as follows:
To protect the operating personnel from the danger of shock.
To maintain the line voltage constant, under unbalanced load condition.
To avoid risk of fire due to earth leakage current through unwanted path.
Protection of the equipments.
Protection of large buildings and all machines fed from overhead lines against lighting.
Methods of Earthing:
The various methods of earthing in common use are,
(a) Plate earthing
12
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – V: BASICS OF POWER SYSTEMS
Earth electrode made of a GI (galvanized iron) pipe of 38mm in diameter and length of
2m (depending on the current) with 12mm holes on the surface is placed upright at a
depth of 4.75cm in a permanently wet ground.
13
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – V: BASICS OF POWER SYSTEMS
To keep the value of the earth resistance at the desired level, the area (15 cm)
surrounding the GI pipe is filled with a mixture of salt and coal.
The efficiency of the earthing system is improved by pouring water through the funnel
periodically.
The GI earth wires of sufficient cross-sectional area are run through a 12.7mm
diameter pipe (at 60cm below) from the 19mm diameter pipe and secured tightly at the
top as shown in figure (5.10).
14
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – V: BASICS OF POWER SYSTEMS
The length of the conductor buried in the ground would give a sufficient earth
resistance and this length should not be less than 15m.
The electrodes shall be as widely distributed as possible in a single straight or circular
trenches radiating from a point.
This type of earthing is used where the earth bed has a rocky soil and excavation work
is difficult.
Selection of Earthing:
The type of earthing to be provided depends on many factors such as type of soil, type
of installation, etc.
The following table helps in selecting a type of earthing for a particular application.
Earth Resistance:
The earth resistance should be kept as low as possible so that the neutral of any
electrical system, which is earthed, is maintained almost at the earth potential.
The earth resistance for copper wire is 1Ω and that of GI wire less than 3Ω.
The typical value of the earth resistance at large power stations is 0.5Ω , major
substations is 1Ω, small sub stations is 2 Ω and in all other cases 5Ω.
The resistance of the earth depends on the following factors:
Condition of soil.
Moisture content of soil.
Temperature of soil.
15
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – V: BASICS OF POWER SYSTEMS
16
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – V: BASICS OF POWER SYSTEMS
b) Materials:
Materials used are tin lead or silver having low melting points. Use of copper or iron is
dangerous, though tinned copper may be used.
c) Types of Fuses:
Fuses are classified into following types,
1. Re-wireable or kit-Kat fuse
2. High rupturing capacity (H.R.C) cartridge fuse
1. Re-wireable or Kit-Kat Fuse:
Re-wireable fuse is used where low values of fault current are to be interrupted.
These fuses are simple in construction, cheap and available up to a current rating of
200A.
They are erratic in operation and their performance deteriorates with time.
An image of re-wireable fuse is as shown in figure (5.12)
When a fault occurs, the current increases and the fuse element melts before the fault
current reaches its first peak.
The heat produced in the process vaporizes the melted silver element.
The chemical reaction between the silver vapours and the filling powder results in the
formation of a high resistance substance which helps in quenching the arc.
8. CIRCUIT BREAKER:
Electrical circuit breaker is a switching device which can be operated manually and
automatically for the controlling and protection of electrical power system, respectively.
During shirt circuits fault or any other type of electrical fault, these equipments, as
well as the power network, suffer a high stress of fault current, which in turn damage
the equipment and networks permanently.
For saving these equipment and the power networks, the fault current should be
cleared from the system as quickly as possible.
Again after the cleared, the system must come to its normal working condition as soon
as possible for supplying reliable quality power to the receiving ends.
The circuit breaker is the special device all the required switching operations during
current carrying condition.
18
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – V: BASICS OF POWER SYSTEMS
A circuit breaker essentially consists of fixed and moving contacts, called electrodes.
Under normal operating conditions, these contacts remain closed and will not open
automatically until and unless the system becomes faulty.
The contacts can be opened manually or by remote control whenever desired.
When a fault occurs in any part of the system, the trip coils of the breaker get
energized and the moving contacts are pulled apart by some mechanism, thus opening
the circuits.
The main types of circuit breakers are,
Miniature circuit breakers (MCB)
Molded Case Circuits Breakers (MCCB)
Earth leakage circuit breakers (ELCB) or Residual Current Breaker (RCCB)
Air blast Circuits Breaker (ACB)
Vacuum Circuits Breaker (VCB)
SF6 Circuits Breaker.
9. MINIATURE CIRCUIT BREAKERS (MCB)
Minimum circuit breakers are electromechanical devices which protect an electrical
circuit from over currents.
Over currents in an electrical circuit may results from short circuits overload, or faulty
design.
MCB is better alternative than fuse, since it does not require replacement once an
overload is detected.
MCB functions by interrupting the continuity of electrical flow through the circuits
once a fault is detected.
In simple terms, MCB is a switch which automatically turns off when the current
flowing through it passes the maximum allowable limit.
Generally MCB is designed to protect against over current and over temperature faults
(over heating).
Working Principle:
There are two contacts - one is fixed and the other is moveable.
When the current exceeds the predefined limit, a solenoid forces the moveable contact
to open (i.e., disconnect from the fixed contact) and the MCB turns off, thereby
stopping the current from flowing in the circuits.
19
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – V: BASICS OF POWER SYSTEMS
Operation:
An image of MCB is shown in figure (5.15) and internal parts of an MCB are shown in
figure (5.16).
It mainly consists of one bi- metallic strip, one trip coil and one hand operated on-off
lever.
Electric current carrying path of a MCB is as follows - first left hand side power
terminal-then bimetallic strip - then current coil - then moving contact - then fixed
contact and lastly right hand side power terminal, and all are arranged in series.
20
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – V: BASICS OF POWER SYSTEMS
The current coil or trip coil placed in such a manner that during SC faults, the MMF of
that coil causes its plunger to hit the same latch point and force the latch to be
displaced. Hence, the MCB will open in the same manner.
Again when operating lever of the MCB is operated by hand, that means when we
make the MCB at off position manually, the same latch point is displaced as a result
moving contact separated from fixed contact in same manner.
So, whatever may be the operating mechanism, i.e., may be due to deformation of bi-
metallic strip or may be due to increased MMF of trip coil or may be due to manual
operation - actually the same latch point is displaced and the deformed spring is
released, which is ultimately responsible for movement of the moving contact.
When the moving contacts are separated from fixed contact, there may be a high
chance of arc.
This are then goes up thorough the arc runner and enters into arc splitters and is
finally quenched.
When we switch on the MCB, we actually reset the displaced operating latch to its
previous on position and make the MCB ready for another switch off or trip operation.
These are available in single pole, double pole, triple pole, and four pole versions with
neutral poles, if required.
The normal current ratings are available from 0.5-63 A with a sym-metrical short
circuits rupturing capacity of 3-10kA, at a voltage level of 230/440v.
MCBs are generally designed to trip within 2.5 millisecond when an over current fault
arises.
In case of temperature rise or over heating it may take 2 seconds to 2 min for the MCB
to trip.
Advantages:
MCBs are replacing the re-wireable switch i.e., fuse units for low power domestic and
industrial applications.
The disadvantages of fuses, like low SC interrupting capacity (say 3kA), Etc, are
overcome with high SC breaking capacity of 10kA.
MCB is combination of all three functions in a wiring system like switching, overload
and short circuits protection. Overload protection can be obtained by using bi-metallic
strips where as shorts circuit protection can be obtained by using solenoid.
21
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – V: BASICS OF POWER SYSTEMS
Voltage –ELCB is a voltage operated circuits breakers. The device will function when
the current passes through the ELCB.
Voltage-ELCB contains relay coil and one end of the coil is connected to metallic load
body and the other end is connected to ground wire as shown in figure (5.17).
If the voltage of the equipment body rises (by touching phase to metal part or
insulation failure of equipment), which could cause the difference between earth and
load body voltage, and the danger of electric shock will occur.
This voltage difference will produce an electric current from the load metallic body and
phase through the loop to the Earth.
When voltage on the equipment metallic body rises to danger level i.e., which exceed to
50V, the flowing current through relay loop could move the relay contact by
disconnecting the supply current and avoid from any danger electric shock.
22
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – V: BASICS OF POWER SYSTEMS
The ELCB detects fault currents from line to the earth (ground) wire within the
installation it protects.
If sufficient voltage appears across the ELCB’s sensing coil, it will switch off the power,
and remain off until manually reset.
A voltage – sensing ELCB does not sense fault current from line to any other earthed
body.
MCCB are manufactured such that the end user will not have access to internal
workings of the over-current protection device.
Generally constructed of two pieces of heavy-duty electrically insulated plastic, these
halves are riveted together to form the whole.
Inside the plastic shell is series of thermal elements and a spring-loaded trigger.
When the thermal element gets too warm, from an over current situation, the spring
trips, which in turn will shut off the electrical circuits.
Operating mechanism:
At its core, the protection mechanism employed by MCCBs is based on the same
physical principles used by all type of thermal – magnetic circuit breakers.
Overload protection is accomplished by means of a thermal mechanism.
MCCBs have a bimetallic contact that expands and contacts in response to changes on
temperature.
Under normal operating conditions, the contact allows electric current through the
MCCB.
However as soon as the current exceeds the adjusted trip value, the contact will start
to heat and expend until the circuits is interrupted.
The thermal protection against overload is designed with a time delay to allow short
duration over current, which is a normal part of operation for many devices.
Fault protection is accomplished with electromagnetic induction, and the response is
instant.
Fault currents should be interrupted immediately, no matter if their duration is short
or long.
Whenever a fault occurs, the extremely high current induces a magnetic field in a
solenoid coil located inside the breaker – this magnetic induction trips a contact and
current it interrupted.
As a complement to the magnetic protection mechanism, MCCBs have internal arc
dissipation measure to facilitate interruption.
As with all types of circuit breakers, the MCCB includes a disconnection switch which
is used to trip the breaker manually.
It is used whenever the electric supply must be disconnected to carry out field work
such as maintenance or equipment upgrades.
25
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – V: BASICS OF POWER SYSTEMS
Applications:
Molded case circuits breakers can have very high current ratings, which allows them
to be used in heavy duty applications. Such as,
Main electric feeder protection
Capacitor bank protection
Generator protection
Welding applications
Low current application that require adjustable trip setting
Motor protection
26
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – V: BASICS OF POWER SYSTEMS
Always make sure that the power source should be shut-off before performing any
work related to electricity.
For example; inspecting, installing, maintaining or repairing.
Running extension cords through the house can trip up residence; this can cause
injury and damage to the wire or outlet if it causes the cord to be ripped out of the
wall.
If you find yourself using extension cords very often, consider having an electrician
install new outlets throughout your home.
Never try repairing energized equipment. Always check that it is de-energized first by
using a tester.
When an electric tester touches a live or hot wire, the bulb inside the tester lights up
showing that an electrical current is flowing through the respective wire.
Check all the wires, the outer metallic covering of the service panel any other hanging
wires with an electrical tester before proceeding with your work.
27
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – V: BASICS OF POWER SYSTEMS
28
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – V: BASICS OF POWER SYSTEMS
TWO MARKS
29
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – V: BASICS OF POWER SYSTEMS
31
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – V: BASICS OF POWER SYSTEMS
34
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – V: BASICS OF POWER SYSTEMS
The device features two arrangements, one for the over current and one for the over-
temperature.
39. Mention the similarity between MCB and MCCB.
They both provide an element of protection
The MCB and MCCB sense and protect the power circuit from the short circuit or
over current situation.
They are mostly used in low tension or low voltage circuit.
40. Give the advantages of MCCB.
MCCB has an adjustable trip setting.
It can interrupt very large currents.
It has a movable trip unit.
It has a very small tripping time thus fast switching during fault current.
It also offers remote ON/OFF feature.
It has a compact design & takes less space.
41. Mention the differences between the MCB and MCCB.
The MCB’s tripping circuit is fixed and is movable in the MCCB.
MCBs have less than 100 amps, while MCCBs have as high as 2,500 amps.
In MCB, the remote on/off is impossible, while in MCCB, it is possible by the use of
shunt wire.
The MCB is largely used in low circuit current, while MCCB is used for the heavy
current circuit.
The MCB is used for low energy requirements (domestic purposes), whereas the
MCCB is used in high energy requirement regions (large industries).
42. What is ELCB?
An Earth-leakage circuit breaker (ELCB) is a safety device used in electrical
installations with high earth impedance to prevent shock. It detects small stray
voltages on the metal enclosures of electrical equipment and interrupts the circuit if
the voltage level exceeds danger threshold.
43. What is the Purpose of ELCB?
The main purpose of ELCB is to detect Earth leakages and prevent injury to human
beings from electrical shocks and prevent electrical fires that are caused by short
Circuit.
35
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – V: BASICS OF POWER SYSTEMS
36