4.2.1.1 Outside Air Intakes Shall: (See Section 6.3 For Smoke Damper Operation To Restrict The Intake of Smoke.)
The document contains standards and guidelines for heating, ventilation and air conditioning (HVAC) systems. It specifies that:
1) Outside air intakes must be protected by corrosion-resistant screens no larger than 0.5 inches and located to minimize smoke and fire introduction. They must have approved dampers.
2) Materials used in HVAC equipment like fans and air conditioners must meet flame spread and smoke development standards, unless otherwise specified.
3) Air supplied to spaces cannot contain hazardous quantities of flammable vapors, flyings or dust. Air outlets must be at least 3 inches above the floor and protected by grilles if lower than 7 feet.
Download as DOCX, PDF, TXT or read online on Scribd
0 ratings0% found this document useful (0 votes)
44 views
4.2.1.1 Outside Air Intakes Shall: (See Section 6.3 For Smoke Damper Operation To Restrict The Intake of Smoke.)
The document contains standards and guidelines for heating, ventilation and air conditioning (HVAC) systems. It specifies that:
1) Outside air intakes must be protected by corrosion-resistant screens no larger than 0.5 inches and located to minimize smoke and fire introduction. They must have approved dampers.
2) Materials used in HVAC equipment like fans and air conditioners must meet flame spread and smoke development standards, unless otherwise specified.
3) Air supplied to spaces cannot contain hazardous quantities of flammable vapors, flyings or dust. Air outlets must be at least 3 inches above the floor and protected by grilles if lower than 7 feet.
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 7
NFPA
4.2.1.1 Outside air intakes shall
be protected by screens of corrosion-resistant material not larger than 12.7 mm (0.5 in.) mesh. 4.2.1.2* Outside air intakes shall be located so as to minimize the introduction of fire or smoke into the building. 4.2.1.2.1 Outside air intakes shall be equipped with an approved fire and/or smoke damper where not located to meet the requirements of 4.2.1.2. (See Section 6.3 for smoke damper operation to restrict the intake of smoke.)
4.2.4.2 Materials. Materials used in the manufacturing of fan coil units, self-contained air- conditioning units, furnaces, heat pumps, humidifiers, and all similar equipment shall meet the requirements of 4.3.3.1 and 4.3.3.2 unless otherwise specified in 4.2.4.2.1 or 4.2.4.2.2.
4.2.4.2.2 Unlisted solar energy air distribution system components shall be accompanied by supportive information demonstrating that the components have flame spread and smoke developed indexes that are not in excess of those of the air duct system permitted by this standard.
Air supplied to any space shall not contain
flammable vapors, flyings, or dust in quantities and concentrations that would introduce a hazardous condition Air outlets shall be located at least 76 mm (3 in.) above the floor, unless provisions have been made to prevent dirt and dust accumulations from entering the system. Where located less than 2.13 m (7 ft) above the floor, outlet openings shall be protected by a grille or screen having openings through which a 12.7 mm (12 in.) sphere cannot pass.
4.3.8.1 General.Air shall not be recirculated from any space in which flammable vapors, flyings, or dust are present in quantities and concentrations that would introduce a hazardous condition into the return air system.
Air inlets shall be constructed of noncombustible material or a material that has a maximum flame spread index of 25 and a maximum smoke developed index of 50 when tested in accordance with ASTM E 84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials.
Air inlets shall be located at least 76 mm (3 in.) above the floor, unless provisions have been made to
prevent dirt and dust accumulations from entering the system. 4.3.8.3.2 Where located less than 2.13 m (7 ft) above the floor, inlet openings shall be protected by a grille or screen having openings through which a 12.7 mm (12 in.) sphere cannot pass. Construction of Air Inlets. Air inlets shall be constructed of noncombustible material or a material that has a maximum flame spread index of 25 and a maximum smoke developed index of 50 when tested in accordance with ASTM E 84,
Coverings and linings for air ducts, pipes, plenums, and panels, including all pipe and duct insulation materials, shall not flame, glow, smolder, or smoke when tested in accordance with ASTM C 411,
UL installation: 4 Installation and operating instructions
4.1 A copy of the installation and operating instructions intended to accompany each unit or component, or equivalent information, shall be included in the examination and test of the equipment. For this purpose, a draft, rather than a printed edition, is acceptable.
4.2 If a unit containing an indoor coil has no provision for connecting a return air duct, or if the instructions indicate that a return air duct need not be used, the instructions may indicate that applicable installation codes can limit this unit to installation only in a single story residence.
4.3 Applicable installation codes or CSA C22.1 or ANSI/NFPA No. 70 can limit the number of eldwiring system connections. See Connection to Power Supply, Clause 17 of this Standard.
4.4 Equipment intended to utilize carbon dioxide (R744) in a secondary loop or a cascade system shall provide instructions indicating that:
a) if the system is de-energized, venting of the R744 through the pressure-regulating relief valves on the equipment can occur. In such cases, the system might need to be recharged with R744, but in any case, the pressure-regulating relief valve(s) shall not be defeated or capped. The relief setting shall not be altered.
b) a sufficient number of pressure-relief and pressure-regulating relief valves may need to be provided based on the system capacity and located such that no stop valve is provided between the relief valves and the parts or section of the system being protected.
c) if the equipment contains a pressure vessel but the pressure-regulating and -relief valves are not installed as part of the equipment as permitted by the Exception to Clause 34.29, the instructions shall specify:
1) the method for installing the valves within the ttings,and
2) that the equipment must be provided with an adequate number of pressure regulating and relief valves based on the system capacity and located such that no stop valve(s) are provided between the relief valve(s) and the parts or section of the system being protected.
CONSTRUCTION
5 Enclosures
5.1 Enclosures for electrical equipment shall be so formed and assembled that, if abused during shipment, installation, or use, they will have the strength and rigidity to resist such abuses without increasing their reand accident hazards due to a total or partial collapse that could result in a reduction of spacings, a loosening or displacement of parts, or any other defect.
5.2 Enclosures for individual electrical components and wiring, outer enclosures, and combinations of the two, shall be considered in determining compliance with the requirements of Clause 5.1.
5.3 Among the factors to be used in determining the acceptability of an enclosure are
a) physical strength;
b) resistance to impact;
c) moisture-absorptive properties;
d) ammability;
e) resistance to corrosion; and
f) resistance to distortion or melting caused by the temperatures that may be expected under conditions of anticipated use or by electrical disturbances within.
5.6 A sheet metal enclosure shall be evaluated with respect to its size, shape, metal thickness, and use in a particular application. Sheet steel having a thickness of less than 0.51 mm (0.020 in) if uncoated or 0.58 mm (0.023 in) if galvanized, or nonferrous sheet metal having a thickness of less than 0.58 mm (0.023 in) are not acceptable, except for relatively small areas or for surfaces that are curved or corrugated, or otherwise reinforced such as by angles, channels, anges, or ribs.
Table 6.1, 6.2, 6.3 for the enclosures
5.7 The enclosure of a unit shall be provided with means for mounting in the intended manner. Any special ttings necessary for intended mounting shall be shipped with the unit. A free-standing, oor-supported unit need not be provided with mounting means. A unit designed for installation in a manufactured (mobile) home shall have provision for permanent mounting.
5.8 An electrical part within the outer cabinet need not be individually enclosed if the assembly complies with all of the following:
a) The construction and location of the part do not permit the emission of ame or molten metal through openings in the outer cabinet, or it can be shown that malfunction of the component does not result in a risk of re.
b) There are no openings in the bottom of the compartment in which the part is located that permit molten metal or the like to drop onto ammable material. See Clause 20.10 on units for outdoor installation.
c) The part is not near ammable material other than electrical insulation.
d) Sheet metal thickness of the outer cabinet is in compliance with Clause 6.
e) The part is not located in an air-handling compartment.
f) The part is not subject to unintended contact by persons, as speci edin Clause 7.
g) There are no openings in the top surface of the outer cabinet that would permit objects to fall on or near uninsulated live parts.
Exception: Motors, electric resistance heating elements, metal-case capacitors, and other similar components that would not emit smoke or components protected to prevent emission of smoke into the air-handling compartment need not be individually enclosed
5.9 To determine if a product complies with Clause 5.8, all of its intended mounting positions shall be considered. For this purpose an air lteris not considered to be part of the enclosure. Isolation From Ignition Sources
5.10.5 Ignition sources within the unit are considered to be insulated or uninsulated live parts such as:
a) hazardous voltage circuit wiring;
b) hazardous voltage electrical components (some examples are; switches, relays, transformer windings, motor windings etc).
polymer
7.1 Uninsulated live parts, excluding lm-coated wire, of hazardous voltage circuits shall be located, guarded, or enclosed so as to prevent unintended contact by persons reaching through openings in the enclosure, or by persons oiling motors, replacing air lters, adjusting controls, or performing other intended service and maintenance operations.
7.2 Openings in enclosures, including perforations, louvres, and openings protected by means of screening, expanded metal, or perforated covers, shall be of such size or shape as to prevent the passage of a probe, illustrated in Figure 7.1, from contacting uninsulated live parts. The con gurationof the probe shall be changed (articulated) after insertion. See Clause 7.6 for lm-coatedwire.
7.3 During the examination of a unit or part thereof, in connection with the requirements in Clause 7.1, parts of the enclosure, such as covers, panels, and grilles shall be removed unless tools are required for their removal. A warning marking, such as speci edin Clause 37.3(r), shall be disregarded in establishing compliance with these requirements.
7.4 In the case of downow units provided with open coil elements that do not comply with Clause 5.8, the manufacturers installation instructions shall specify that an L-shaped exhaust duct be used as a bottom closure, without any outlets or registers located directly below open coil elements.
Exception: An acceptable barrier is considered to be provided by a nnedcoil construction at least two rowsindepthandwithatleast12 nsper25.4mm(1in).
7.5 With reference to Clause 7.4, an air lteris not acceptable as a barrier.
7.6 A probe as illustrated in Figure 7.2 shall not touch lm-coated wire when inserted through the opening.
8.1 Doors and covers that give access to uninsulated live hazardous voltage parts shall be secured rmly in place, and shall require the use of a tool or key to open them or shall be provided with an interlocking mechanism; except that components having covers that comply with their respective standards do not require additional enclosures.
8.2 An interlocking mechanism complies with the requirements of Clause 8.1 if it
a) secures the cover in the closed position when engaged;
b) must be engaged before parts in a hazardous voltage circuit can be energized; and
c) is located so that unintentional operation is unlikely during normal servicing.
8.3 An interlock that is required to reduce a risk of electric shock or injury to persons shall withstand 1000 cycles with a load not less than that controlled in the equipment, and 5,000 cycles without a load, or shall comply with CSA-C22.2 No. 55; and UL 353
8.4 An interlock that is required to reduce the risk of electric shock shall open all supply conductors.
9.1Sufficient and reasonable accessibility shall be afforded to all parts that require normal servicing or adjustment (for example, controls, lters, oiling of bearings, adjustment of belts) when the equipment is installed as intended. Covers or access panels giving access to such parts that are required to be removed for routine maintenance shall not expose uninsulated hazardous voltage live parts
11.1 All moving parts (for example, fan blades, blower wheels, pulleys, and belts) that, if accidentally contacted, could cause bodily injury, shall be guarded against accidental contact by an enclosure or screen requiring tools for removal, or permanently attached.
11.3 An interlocking mechanism that operates to disconnect power to the drive motor when a cover or panel is removed or opened to provide access to moving parts is considered to provide the protection required by Clause 11.1