SD-365 Data Sheet
SD-365 Data Sheet
SD365(A) Series
Addressable Photoelectric Detectors
Addressable Devices
General
The Fire-Lite SD365(A), SD365T(A), and SD365R(A) Series
addressable plug-in photoelectric smoke detectors are designed for
both performance and aesthetics. A new modern, sleek, contempo-
rary design and enhanced optical sensing chamber is engineered to
sense smoke produced by a wide range of combustion sources in
accordance with more stringent code standards.
Exclusively for use with Fire-Lite’s addressable fire alarm control
panels, the SD365(A) Series point ID capability allows each detec-
tor’s address to be set with rotary, decimal address switches, provid-
ing exact detector location for emergency personnel to quickly locate
a fire during its early stages, potentially saving precious rescue time
while also reducing property damage. Two LEDs on each sensor
light to provide a local, visible sensor indication.
The SD365(A) Series also offers 135°F (57°C) fixed temperature
thermal sensing on the SD365T(A) and a remote test capable detec-
tor on the SD365R(A) for use with DNR(A)/DNRW duct smoke
detector housings.
SD365
Features
SLC LOOP
• Two-wire loop connection.
Installation
• Unit uses base for wiring. SD365(A) series plug-in detectors use a detachable mounting base
to simplify installation, service and maintenance.
ADDRESSING Mount base (all base types) on an electrical backbox which is at
• Addressable by device. least 1.5" (3.81 cm) deep. For a chart of compatible junction boxes,
• Rotary, decimal addressing: Please refer to the Fire-Lite panel see DF-60059.
manuals for device capacity. NOTE: Because of the inherent supervision provided by the SLC loop,
end-of-line resistors are not required. Wiring “T-taps” or branches are
ARCHITECTURE permitted for Style 4 (Class B) wiring. SD365R(A) mounts in a
• New modern profile for improved aesthetics. D355PL(A) or DNR(A) /DNRW duct detector housing.
• Unique single-source design to respond quickly and dependably
to a broad range of fires. Operation
• Integral communications and built-in type identification. Each SD365(A) Series detector uses one possible addresses on the
• Built-in tamper-resistant feature. Fire-lite Signaling Line Circuit (SLC). It responds to regular polls
• Removable cover and insect-resistant screen for simple field from the system and reports its type and status.
cleaning.
Detector Sensitivity Test
OPERATION
Each detector can have its sensitivity tested (required per NFPA 72,
• Designed to meet UL 268 7th Edition. Chapter 14 on Inspection, Testing and Maintenance) when installed/
• Factory preset at 1.5% nominal sensitivity for panel alarm thresh- connected to an ES-50X or ES-200X addressable fire alarm control
old level. panel. The results of the sensitivity test can be printed off the for
• Visible LED “blinks” when the unit is addressed (communicating record keeping.
with the fire panel) and latches on in alarm.
• Low standby current. Specification
MECHANICALS Voltage range: 15 – 32 VDC (peak).
• Sealed against back pressure. Standby current: 200 μA @ 24 VDC.
• Mounts to: single-gang box, 3.5" (8.89 cm) or 4.0" (10.16 cm) Max current: 4.5 mA @ 24 VDC (latched “ON”).
octagonal box, or 4.0" (10.16 cm) square electrical box (with or Air velocity: 4,000 ft./min. (20 m/sec.) maximum.
without a mud ring - not included).
Sensitivity: UL Applications: 0.5% to 4.0% per foot obscuration
OPTIONS Size: 2.0" (5.3 cm) high; base determines diameter.
• Remote LED output connection, RA100Z.
– B300-6: 6.1" (15.6 cm) diameter.
– B501: 4" (10.2 cm) diameter.
For a complete list of detector bases see DN-60981.
Shipping weight: 3.4 oz. (95 g).
NOTE: Detectors must be mounted to one of the Intelligent Bases listed B200SCOA-IV: Ivory Intelligent, programmable sounder base in
below. English/French (required in Canada for ULC applications with CO
Series detector applications, ULC listing.
NOTE: “IV” suffix indicates LiteSpeed® and CLIP device.
B200S-LF-WH: White, Low Frequency Intelligent, programmable
NOTE: “A” suffix indicates Canadian version.
sounder base. Produces a fundamental frequency of 520 Hz +/-
SD365(A): White, Addressable photoelectric detector; B300-6 base 10% with a square wave or its equivalent; designed to meet the
included. LiteSpeed only. NFPA 72 sleeping space requirement. (CSFM: 7300-1653:0238
SD365(A)-IV: Ivory, Addressable photoelectric detector; B300-6 Pending)
base included. B200S-LF-IV: Ivory, Low Frequency Intelligent, programmable
SD365T(A): White, Same as SD365 but with thermal element; sounder base. Produces a fundamental frequency of 520 Hz +/-
B300-6 base included. LiteSpeed only. 10% with a square wave or its equivalent; designed to meet the
NFPA 72 sleeping space requirement. (CSFM: 7300-1653:0238
SD365T(A)-IV: Ivory, Same as SD365 but with thermal element; Pending)
B300-6 base included.
B200SR-WH: White, Intelligent sounder base capable of producing
SD365R(A): White, Remote test capable addressable photoelectric sound output with ANSI Temporal 3 or continuous tone. Intended for
detector for use with DNR(A)/DNRW. LiteSpeed only. retrofit applications. (CSFM: 7300-1653:0213 Pending)
SD365R(A)-IV: Ivory, Remote test capable addressable photoelec- B200SR-IV: Ivory, Intelligent sounder base capable of producing
tric detector; for use with DNR(A)/DNRW. sound output with ANSI Temporal 3 or continuous tone. Intended for
retrofit applications. (CSFM: 7300-1653:0213 Pending)
INTELLIGENT BASES
NOTE: For details on intelligent bases, see DN-60981. B200SRA-WH: Same as B200SR-WH with, ULC listing.
B300-6: White, 6” base, standard flanged low-profile mounting base. B200SRA-IV: Same as B200SR-IV in Ivory color, ULC listing.
(CSFM: 7300-1653:0109 Pending) B200SR-LF-WH: White, Low Frequency Intelligent, programmable
B300-6-IV: Ivory,6” base, standard flanged low-profile mounting sounder base. Produces a fundamental frequency of 520 Hz +/-
base. (CSFM: 7300-1653:0109 Pending) 10% with a square wave or its equivalent; designed to meet the
NFPA 72 sleeping space requirement. Intended for retrofit applica-
B300A-6: Same as B300-6, ULC listed. tions. (CSFM: 7300-1653:0238 Pending)
B300A-6-IV: Ivory, 6” standard flanged low-profile mounting base, B200SR-LF-IV: Ivory, Low Frequency Intelligent, programmable
ULC listed. sounder base. Produces a fundamental frequency of 520 Hz +/-
B300-6-BP: Bulk pack of B300-6, package contains 10 10% with a square wave or its equivalent; designed to meet the
NFPA 72 sleeping space requirement. Intended for retrofit applica-
B501-WHITE: White, 4” standard European flangeless mounting
tions. (CSFM: 7300-1653:0238 Pending)
base. UL/ULC listed. (CSFM: 7300-1653:0109 Pending)
B501-BL: Black, 4” standard European flangeless mounting base. MOUNTING KITS AND ACCESSORIES
UL/ULC listed. (CSFM: 7300-1653:0109 Pending) TR300: White, replacement flange for B210LP(A) base.
B501-IV: Ivory color, 4” standard European flangeless mounting TR300-IV: Ivory, replacement flange for B210LP(A) base.
base. UL/ULC listed. (CSFM: 7300-1653:0109 Pending)
RA100Z(A): Remote LED annunciator. 3 – 32 VDC. Mounts to a
B501-WHITE-BP: Bulk pack of B501-WHITE contains 10. U.S. single-gang electrical box. For use with B501(A) and B300-
B224RB-WH: White, relay base. (CSFM: 7300-1653:0216 Pending) 6(A).
B224RB-IV: Ivory, relay base. (CSFM: 7300-1653:0216 Pending) M02-04-00: Test magnet.
B224RBA-WH: White, relay base, ULC listing. M02-09-00: Test magnet with telescoping handle.
B224RBA-IV: Ivory, relay base, ULC listing. CK300: Color Kit (includes cover and trim ring), white, 10-pack.
B224BI-WH: White, isolator detector base. (CSFM: 7300- CK300-IV: Color Kit (includes cover and trim ring), ivory, 10-pack.
1653:0216 Pending) CK300-BL: Color Kit (includes cover and trim ring), black, 10-pack.
For more information, contact Fire•Lite Alarms. Phone: (800) 627-3473, FAX: (877) 699-4105.
www.firelite.com