Build Your Reputation On Ours: Fan Coil Technical Catalog
Build Your Reputation On Ours: Fan Coil Technical Catalog
2 Table of Contents
3-4 Portfolio
5
Features & Benefits
7
Ratings & Listings
8 Air Delivery
9
Sound Data
14 Electric Heating
15 Motor Data
o Horizontal Telescoping Hideaway units with • Optional condensate overflow switch to address latest
painted access panel (CBY) allows smooth fit up building codes where required.
to plaster or sheet rock ceilings. Standard units • Wide variety of optional insulation materials are
include bottom louvered return air with the filter available to address IAQ concerns.
located in the access panel.
o Horizontal Hideaway models (CHY) units are Ease of Installation
installed above the ceiling with or without ducted • Factory assembled valve packages minimize piping
supply air and open “soffit” return with an optional work at the job site (shipped loose for field mounting).
ceiling-mounted filter-grille. • Optional unit mounted controls, service switches and
o Horizontal Hideaway models with plenum (CPY) fusing minimize the electrical work required on site.
units are installed above the ceiling with or • Units are tagged at the factory for clear identification
without ducted supply air and ducted return air.
on job site.
The return air filter is either mounted on the unit
• Opposite end connection units may minimize the
plenum or installed in an optional ceiling filter-
piping work on renovation jobs.
grille.
Hand*** Arrangement
Two-pipe Cooling and Heating Four-pipe Coil Coil
or Four-pipe Cooling Heating Connection Construction R • Right 5
L • Left 6
A • 3 Row R • 3 Row, AAV Y • None Y • None Y • Std
B • 4 Row S • 4 Row, AAV 6 • 1 Row S • Same End S • SS Wrapper
D • 2 Row 7 • 2 Row O • Opposite End 6
CHY, BHY
CXB
5
Voltage System
B • 24 V Manual Fan Operation Thermostat
C • 120 V A • Standard Wall Mount (Switch Only) A •
TB155 Wall Series, ACO, Vertical Mnt.
D • 208 V B •
TB155 Wall Series, ACO, Horizontal Mtd.
E • 240 V Function Control P •
Basic 24V Digital Programmable, ACO
F • 277 V G • 2 Pipe Heat Only N •
Basic 24V Non-Programmable, ACO
V • 220 V (50)* H • 2 Pipe Cool Only F •
Premium 24V Digital 7-Day Programmable,
U • 240 V (50)* K • 2 Pipe Heat and Cool with Proportional Fan/Valves Option, ACO
M • 2 Pipe Heat and Cool w/Aux. Elec. Heat G • Premium 24 Digital BACnet with
* Consult factory for 50Hz applications. P • 2 Pipe Cool Only w/Total Elec. Heat Proportional Fan/Valves Option, ACO
** Note that kWs depend on voltage R • 4 Pipe Heat and Cool
and unit size.
*** Standing in front of the unit, hand is
determined by looking into the air supply
and assigning the hand to match the
location of the cooling coil connections.
standards.
Standard Ratings
Cooling Capacity Power
Unit Unit Cell Nominal
Total Sensible Input
Type Size CFM
MBH MBH Watts PSC
02-A 200 6.0 4.4 87
03-A 300 9.0 6.3 85
CHY 04-A 400 12.1 8.8 165
CPY
06-A 600 17.3 13.0 225
CXB
CBY 08-A 800 22.6 16.2 235
10-A 1000 27.5 21.0 305
12-A 1200 32.8 25.0 450
02-B 200 6.9 4.3 87
03-B 300 9.8 6.5 85
CHY 04-B 400 13.8 9.8 145
CPY
06-B 600 19.6 14.3 220
CXB
CBY 08-B 800 25.5 18.8 235
10-B 1000 31.0 22.0 300
12-B 1200 37.2 27.7 425
NOTES: 1. Ratings are based on 80°F DB and 67°F WB EAT, 45°F
EWT, 10°F water temperature rise, high fan speed,
motor voltage 115/1/60, and air flow under dry coil
conditions.
2. For all application ratings, use IEC’s computer selection
program, the quick-selection ratings provided in this
catalog, or contact your local IEC representative.
3. For additional information, please consult AHRI’s
website at www.ahrinet.org.
Sound Data
SOUND POWER LEVEL, Lw (dB one reference pico watt)
UNIT FAN
RATING CFM A-wgt
SIZE SPEED 125 Hz 250 Hz 500 Hz 1K Hz 2K Hz 4K Hz 8K Hz
(dBA)
H 270 60 54 51 48 43 38 37 53
CASING
M 170 55 51 44 39 35 31 34 47
RADIATED
L 135 53 49 39 34 29 29 34 44
2
H 270 52 52 53 47 46 40 37 54
DUCTED
M 170 47 45 45 39 37 31 34 46
DISCHARGE
L 135 46 43 40 33 31 29 34 42
H 290 63 54 52 49 44 40 38 54
CASING
M 205 59 47 44 40 35 31 34 47
RADIATED
L 155 55 42 39 34 29 29 34 43
3
H 290 59 54 54 51 47 41 38 56
DUCTED
M 205 55 46 47 41 37 31 34 48
DISCHARGE
L 155 51 42 42 35 31 29 34 43
H 540 70 58 55 52 48 43 39 58
CASING
M 360 62 49 46 42 37 32 34 50
RADIATED
L 250 54 42 38 32 30 30 34 42
4
H 540 64 57 59 55 50 44 39 60
DUCTED
M 360 55 49 51 52 46 36 36 50
DISCHARGE
L 250 48 42 43 35 30 28 33 43
H 680 65 59 57 52 48 45 42 59
CASING
M 445 57 50 47 41 37 33 34 49
RADIATED
L 330 52 43 40 34 29 29 34 43
6
H 680 63 58 59 56 50 46 42 60
DUCTED
M 445 57 49 50 45 39 33 34 50
DISCHARGE
L 330 53 43 42 37 30 29 34 44
H 765 65 61 58 54 51 48 45 60
CASING
M 670 63 58 55 51 47 44 41 57
RADIATED
L 410 55 47 44 38 34 31 34 46
8
H 765 63 61 61 58 53 50 46 63
DUCTED
M 670 60 58 58 54 50 46 42 59
DISCHARGE
L 410 52 47 47 41 36 32 35 48
H 1105 68 64 59 55 52 48 45 62
CASING
M 730 64 55 51 45 41 37 35 54
RADIATED
L 490 59 48 43 36 31 30 34 47
10
H 1105 65 62 64 60 55 50 46 65
DUCTED
M 730 63 54 56 50 44 38 36 56
DISCHARGE
L 490 58 46 47 40 33 30 34 48
H 1225 68 65 61 57 53 50 45 63
CASING
M 1140 67 63 59 54 51 47 42 61
RADIATED
L 745 59 54 50 44 40 35 34 52
12
H 1225 65 63 65 60 57 52 47 66
DUCTED
M 1140 63 61 63 58 54 50 44 64
DISCHARGE
L 745 56 54 55 48 43 37 35 54
0.45
0.4
0.35 High
0.3
ESP (in.W.C.)
0.25 Med
0.2
0.15 Low
0.1
0.05
0
0 50 100 150 200 250 300 350
SCFM
PSC Motor Fan Curve:
- 3-Row 5-Row
ECM Operating Range:
4-Row
0.45
0.4
0.35 High
0.3
ESP (in.W.C.)
0.25 Med
0.2
0.15 Low
0.1
0.05
0
0 50 100 150 200 250 300 350 400 450
SCFM
PSC Motor Fan Curve: 3-Row 5-Row
ECM Operating Range:
4-Row
0.45
0.4
0.35 High
0.3
ESP (in.W.C.)
0.25 Med
0.2
0.15 Low
0.1
0.05
0
100 150 200 250 300 350 400 450 500 550 600 650
SCFM
PSC Motor Fan Curve:
- 3-Row 5-Row
ECM Operating Range:
4-Row
0.45
0.4
0.35 High
0.3
ESP (in.W.C.)
0.25 Med
0.2
Low
0.15
0.1
0.05
0
100 150 200 250 300 350 400 450 500 550 600 650 700 750
SCFM
PSC Motor Fan Curve: 3-Row 5-Row ECM Operating Range:
4-Row
0.45
0.4
0.35 High
0.3
ESP (in.W.C.)
0.25 Med
0.2
Low
0.15
0.1
0.05
0
200 250 300 350 400 450 500 550 600 650 700 750 800 850
SCFM
- 3-Row
PSC Motor Fan Curve: 5-Row
ECM Operating Range:
4-Row
0.45
0.4
0.35 High
0.3
ESP (in.W.C.)
Med
0.25
0.2
Low
0.15
0.1
0.05
0
350 400 450 500 550 600 650 700 750 800 850 900 950 1000 1050 1100 1150 1200 1250
SCFM
PSC Motor Fan Curve:
- 3-Row 5-Row
ECM Operating Range:
4-Row
0.45
0.4
0.35 High
0.3
ESP (in.W.C.)
0.25 Med
0.2
0.15 Low
0.1
0.05
0
350 450 550 650 750 850 950 1050 1150 1250 1350 1450 1550
SCFM
PSC Motor Fan Curve:
- 3-Row 5-Row ECM Operating Range:
4-Row
Total electric heat eliminates the requirement for a boiler. 120 V 1.5 • • • • • - -
Heating and/or cooling may be available on an individual 2.0 • • • • • • •
basis throughout the year. Two-pipe chilled water is used
for cooling; and the electric heater is used for heating.
3.0 - • • • • • •
Individual room controls can be supplied for either manual 0.5 • • - - - - -
between the blower and the coil. High limit thermal cutouts 2.0 • • • • • • •
protect the heater in the event of air failure. There are many
240 V
3.0 - • • • • • •
special applications and control sequences for electric heat. 277 V
For special applications, please consult the factory.
4.0 - - - • • • •
5.0 - - - •
Note 6 • • •
6.0 - - - •
Note 6
•
Note 6 • •
8.0 - - - - - •
Note 6
•
Note 6
10.0 - - - - - - •
Note 6
NOTES: 1. All heaters are single stage and single phase.
2. Heaters over 48 Amps are subdivided and fused.
3. Electric Heating Capacities (BTUH) = Heater kW x 3413.
4. Electric Heater Amperage = (Heater kW x 1000)/Applied
Voltage)
5. Consult factory for 50 Hz applications.
6. High and medium speed only.
7-1/3
6 (187)
(152)
1-1/2
(38) 1-1/8 RESILIENT MOUNTING D'
(29) E GROMMET W/ 3/8 (10) OPTIONAL
MTG. HOLES DIA. HOLES (TYP. OF 4) EXTENDED
3 A'
2-1/4 B DRAIN PAN
(57) (76)
A
TOP VIEW
17-1/2
(445)
1"(25)
SUPPLY 8-3/8
H DUCT (213)
3/4 COLLAR
(19) CHILLED/HOT WATER
TYP 7/8 AIR
SUPPLY & RETURN (22) VENT
CONNECTIONS
(SEE SUPPLEMENTAL
DRAWING FOR COIL
STUBOUT SUPPLY
LOCATIONS) G F AIR
OPTIONAL
DRIP LIP
SHIPPED LOOSE
16 (NOTE 4)
(406)
FRONT VIEW RIGHT SIDE VIEW
1-1/2 RESILIENT
(38) MOUNTING
GROMMET D'
1-1/8 W/ 3/8 (10) OPTIONAL
(29) E EXTENDED
MTG. HOLES DIA. HOLES A'
2-1/4 B 3 (TYP. OF 4) DRAIN PAN
(64) (76)
A
TOP VIEW
21-1/2
(546)
12-3/8
H 1"(25) SUPPLY (314)
3/4 DUCT COLLAR
(19) 7/8
TYP CHILLED/HOT WATER (22) AIR
SUPPLY & RETURN VENT
CONNECTIONS
(SEE SUPPLEMENTAL
DRAWING FOR COIL SUPPLY
STUBOUT LOCATIONS) F AIR
G
OPTIONAL DRIP LIP
SHIPPED LOOSE
(NOTE 4)
16
(406)
FRONT VIEW RIGHT SIDE VIEW
20
(508)
19
E CHILLED/HOT 1"(25) SUPPLY (483)
3/4 DUCT COLLAR 11-3/8
(19) WATER SUPPLY & (289)
TYP RETURN CONNECTIONS 7/8
(22) AIR VENT
(SEE SUPPLEMENTAL
DRAWING FOR COIL
STUBOUT LOCATIONS) SUPPLY
F AIR
10-1/2 OPTIONAL DRIP LIP G
(267) SHIPPED LOOSE REAR
(NOTE 4) ACCESS
PANEL
1"(25) FILTER
A 16
(406) RETURN FILTER
AIR REMOVAL
FRONT VIEW RIGHT SIDE VIEW
ELECTRIC 2
(51)
STRIP HEATER
6 ELEMENT
(152) 1"(25)
STD. 1
(25) FILTER
19-1/4 7-1/3
(489) (187) RETURN
AIR
1"(25)
7/8 (22) O.D. RETURN
CONDENSATION OPTIONAL DUCT
DRAIN D' EXTENDED COLLAR
DRAIN
STRIP A' PAN
HEATER FILTER
1-1/2 RETAINER
(38) HIGH LIMIT BOTTOM
1-1/8 ACCESS CLIP
(29) C PANEL FILTER REMOVAL
FRONT MTG. HOLES
2-1/4 B 3
(57) (76)
A
TOP VIEW OPTIONAL REAR RETURN
24
1"(25) (610)
SUPPLY 23
DUCT (584) 11-3/8
CHILLED/HOT COLLAR
3/4 WATER SUPPLY (289)
3/4 (19) RESILIENT MOUNTING GROMMET 7/8 AIR
(19) TYP & RETURN VENT
W/ 3/8 (10) DIA. HOLES (TYP. OF 4) CONNECTIONS (SEE (22)
SUPPLEMENTAL
DRAWING FOR
COIL STUBOUT SUPPLY
10-1/2 LOCATIONS) F AIR
(267) G
OPTIONAL
DRIP LIP REAR
SHIPPED ACCESS
LOOSE PANEL
(NOTE 5) 1"(25) FILTER
ELECTRICAL KNOCKOUTS 16
(406) RETURN FILTER
IN TOP & BOTTOM OF AIR REMOVAL
CONTROL BOX
FRONT VIEW RIGHT SIDE VIEW
24
(610)
11-1/4 SUPPLY 6
F (152)
12 (305) (286) AIR
MIN.
14 (356)
MAX. 1
1"(25) SUPPLY (25)
DUCT COLLAR
HINGED
7/8 (22) O.D. CONDENSATE BOTTOM
D DRAIN CONNECTION RETURN STAMPED RETURN
AIR RETURN AIR PANEL
AIR GRILLE &
1"(25) FILTER
FRONT VIEW RIGHT SIDE VIEW
RESILIENT MOUNTING
GROMMETS
WITH 3/8 (10)
DIA. HOLE 7/8 (22)
(TYP. OF 4) KNOCKOUT
1 1-1/2 (38)
(25)1-1/2 KNOCKOUT
(38) E (TYPICAL)
1 1
(25) (25)
6-1/8 TOP VIEW PARTIAL REAR VIEW
(156) (TYPICAL BOTH SIDES)
24
(610)
11-1/4 SUPPLY
F 6
12(305) (286) AIR (152)
MIN.
14(356)
MAX. 1
1"(25) SUPPLY (25)
DUCT COLLAR
HINGED
7/8 (22) O.D. CONDENSATE STAMPED BOTTOM
D RETURN RETURN
DRAIN CONNECTION AIR RETURN
AIR GRILLE & AIR PANEL
1"(25) FILTER
FRONT VIEW RIGHT SIDE VIEW
CHILLED/HOT WATER
SUPPLY & RETURN
CONNECTION (SEE
SUPPLEMENTAL
36 30-3/4 DRAWING FOR COIL
(914) (781) STUBOUT LOCATIONS)
RESILIENT MOUNTING
GROMMETS WITH
3/8 (10) DIA. HOLE
(TYP. OF 4) 7/8 (22)
1 KNOCKOUT
(25) 1-1/2 (38)
KNOCKOUT
1-1/2 (TYPICAL)
(38) 1-1/2 (38)
E 1-1/2 (38)
1 1
(25) TOP VIEW (25) PARTIAL REAR VIEW
(TYPICAL BOTH SIDES)
1-1/2 34 1-1/2
(38) (864) (38)
A 30-3/4
1-1/2 1-1/2 (781) OPTIONAL
(38) (38) AIR VENT DUCTED
REAR RETURN
11-1/4 6
(286) (152)
12"(305)
MIN.
14"(356) 1
MAX. (25)
HINGED
STAMPED BOTTOM RETURN
D SUPPLY SUPPLY 7/8 (22) O.D. RETURN AIR PANEL
AIR CONDENSATE AIR
AIR GRILLE 6 DRAIN STAMPED RETURN
(152) CONNECTION AIR GRILLE &
1"(25) FILTER
FRONT VIEW RIGHT SIDE VIEW
CBY - Horizontal Telescoping Hideaway with Bottom Supply with Electric Heat
UNIT LABEL
1 CONTROL AND WIRING DIAGRAM
(25) BOX (SEE NOTE 6) ELECTRIC STRIP
1-1/2 STRIP HEATER
(38) HIGH LIMIT HEATER ELEMENT
CHILLED/HOT
WATER SUPPLY
30-3/4 & RETURN
36 (781) CONNECTION (SEE
(914) SUPPLEMENTAL
DRAWING FOR COIL
STUBOUT LOCATIONS)
RESILIENT MOUNTING
GROMMETS WITH
3/8 (10) DIA. HOLE 7/8 (22)
(TYP. OF 4) KNOCKOUT
1 1-1/2 (38)
(25) KNOCKOUT
(TYPICAL)
1-1/2
(38) 1-1/2
E
1-1/2 PARTIAL REAR VIEW
(38) (38) (TYPICAL BOTH SIDES)
1 1
(25) TOP VIEW (25)
34
(864)
2 2
(51) E (51)
2
(51) A PARTIAL REAR VIEW
CHILLED/HOT WATER
TOP VIEW SUPPLY & RETURN
(TYPICAL BOTH SIDES)
CONNECTIONS
(SEE SUPPLEMENTAL
DRAWING FOR COIL
STUBOUT LOCATIONS)
23-1/2
(597)
7/8" (22) O.D.
C B C 1-1/2 AIR VENT CONDENSATE
(38) DRAIN CONNECTION
OPTIONAL
SUPPLY RETURN 5-3/4
F AIR AIR (146)
G LOCATION
APPROX. 2
STANDARD STAMPED RESILIENT MOUNTING REF. (51) STANDARD
SUPPLY AIR GRILLE RETURN STAMPED RETURN
GROMMETS WITH 3/8" (10) REMOVABLE HINGED AIR
R.A./ACCESS AIR GRILLE &
DIA. HOLE (TYP. OF 4) 1" (25) FILTER
PANEL
FRONT VIEW RIGHT SIDE VIEW
2 2
E (51)
(51)
2 A
(51)
CHILLED/HOT WATER
TOP VIEW SUPPLY & RETURN
CONNECTIONS
PARTIAL REAR VIEW
(SEE SUPPLEMENTAL (TYPICAL BOTH SIDES)
DRAWING FOR COIL
STUBOUT LOCATIONS)
23-1/2
(597)
C B C 1-1/2 AIR VENT
(38)
OPTIONAL
SUPPLY RETURN 5-3/4
F AIR AIR
G LOCATION (146)
APPROX. 2
REF. (51) STANDARD
STANDARD STAMPED REMOVABLE HINGED RETURN STAMPED RETURN
SUPPLY AIR GRILLE RESILIENT MOUNTING AIR AIR GRILLE &
GROMMETS WITH 3/8 (10) R.A./ACCESS
PANEL 1"(25) FILTER
DIA. HOLE (TYP. OF 4)
FRONT VIEW RIGHT SIDE VIEW
As detailed in the table on page 27, we offer a control Condensate High Level Switch
for most of the customer needs. Additional controls and
This switch shuts down the unit when the water level in the
devices are available to meet even the most demanding
drain pan reaches an unsafe level. Building code changes in
operating logic.
much of the country now require this type of device.
Three-speed Fan Control
Service Switches
All of our basic control schemes utilize a 2- or 3-speed
We offer concealed service switches for use by maintenance
switch to modulate the cooling output, to maximize the
and service personnel to shut off the power while working
percentage of latent heat removal, and to further minimize
on the unit.
the sound level when maximum cooling or heating
performance is not required. Fusing
Low Voltage Control (24 V) We offer incoming power fusing for all units as well as
A low voltage control is available with all of our control blower motor and control sub-fusing for units that use
Control Packages
24 V Programmable and
Vertical Wall Non-Programmable
Series 155 Digital Series
Thermostat Features
Control Type1
All listed controls include fan switching. Vertical and Horizontal Wall Series
24 V Digital Series
155
24 V, 115 V, 208 V, 240 V, 277 V 24 V only
Remote Wall Mounted
Manual Fan Switch Operation
Auto Fan Speed Control N/A
Continuous 3-Speed Fan
Cycling Fan N/A
O.A. Damper Signal
Remote Temperature Sensor Opt Opt
Adjustable Operating Range Kit
Touch Pad/Digital Display N/A
Local Temperature Set-Back N/A
Water Temperature Purge Cycle N/A
Pipe Sensor N/A
NOTES: 1. Control packages with valve cycle control are continuous fan operation only.
2. All wall-mount control packages are shipped loose for field installation. (Boxes, tile rings, plaster rings, etc. are not provided.)
3. Aquastats are included in control packages, as required.
Control Options
• 24 V control packages • Minimum room temperature thermostats (Special Quote)
• Unit-mounted fan switches (Special Quote) • Low voltage remote shutdown relays (Special Quote)
• Single power source wiring (motor/control fusing) • Fan and valve cycle applications (Special Quote)
• Incoming power fusing • Thermostats available with large letter print for handicap
• Service switches applications (Special Quote)
• DX coil applications
Ball S
R R
Valve Swage
A
(Ships Separate)
Ball
Valve S
Aquastat
Coil
2-way Valve NOTES: 1. Please note that project specifications for system
Ball
pressure, pressure drop limitations and flow rate
S S should be checked prior to selecting specific
Valve
Swage components or the valve package size.
2. The supply and return piping connections of the
factory-provided valve package are either swaged for
field brazing (standard) or union fitted (optional) for
Two-way Motorized Control Valve with connection to the coil.
3. Consult IEC’s Valve Packages and Piping Components
Changeover manual or your local representative for detailed
piping and valve application information. Factory-
In a two-way motorized changeover control valve package, provided valve packages are assembled, brazed,
wired electrically and dry-fit to the coil connections
the motor drives the valve open, and a spring returns the before shipping. Field brazing to the coil completes
valve to a normally closed position. No water flows through the installation. Some applications dictate shipping
isolation valves loose.
the coil with the unit off. The aquastat bypass line allows
a small amount of water to flow from the supply to the
return piping when the control valve is closed. The strap-
on aquastat senses whether the flowing water is cold or
hot and switches a contact closed to provide automatic
summer/winter changeover (ACO) for the system.
Air Vent
R Ball R
Valve
Swage